head_banner_pro

AMC72-E4/KC Multi-Function Power Meter (2DI+2DO)

Application:

Power monitoring and energy metering in three-phase four-wire low-voltage distribution systems.

Suitable for industrial facilities, commercial buildings, utilities and intelligent buildings.

2DI and 2DO can be used for status monitoring and remote control, while RS485 enables connection to power monitoring and energy management systems.

Basic Parameters:

Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V or AC 3×220V/380V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Digital Input: 2DI
Relay Output: 2DO
Energy Pulse Output: 1Ep
Communication: RS485, Modbus-RTU
Auxiliary Power Supply: AC/DC 85–265V
Display: LED Digital Display


Information

Parameter

Function

Download

Characteristic

5

Communication

Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps

6

Display
LED Digital Display
System Time Display
Parameter Setting and Control via Keys

7

Rated U and l
Three-phase Four-wire
Rated Voltage: AC 3×57.7V/100V, AC 3×220V/380V
Rated Current: AC 1A or 5A
Frequency: 45–65Hz
Voltage Overload: 1.2× continuous, 2× for 1s
Current Overload: 1.2× continuous, 10× for 1s

General

AMC72-E4/KC is a 72-size panel-mounted multi-function power meter designed for electrical parameter measurement, energy metering and power monitoring in three-phase four-wire systems.It measures three-phase voltage and current, zero-sequence voltage and current, active, reactive and apparent power, power factor, frequency, voltage phase angle, voltage/current unbalance, forward and reverse power, and four-quadrant energy.This version provides 2 digital inputs, 2 relay outputs, energy pulse output and RS485 Modbus-RTU communication, allowing status monitoring, remote control and integration with power monitoring or energy management systems.

Function

Connection

Three-phase four-wire

Frequency

45–65Hz

Voltage

Rated Voltage: AC 3×57.7/100V, AC 3×220/380V
Overload: 1.2 times rated value continuously; 2 times rated value for 1s
Power Consumption: <0.5VA

Current

Rated Current: AC 1A, 5A
Overload: 1.2 times rated value continuously; 10 times rated value for 1s
Power Consumption: <0.5VA

Accuracy

Voltage: Class 0.2
Current: Class 0.2
Active Power: Class 0.5
Active Energy: Class 0.5
Reactive Power: Class 1.0
Reactive Energy: Class 1.0
Frequency: ±0.05Hz
2nd–31st Harmonics: ±1%

微信图片_20260819093034_58_48
微信图片_20260819093048_59_48

Communication

Interface: RS485
Protocol: Modbus-RTU
Baud Rate: 1200–38400bps

Switching Input

2 Digital Inputs
Dry Contact Input
Built-in Power Supply

Switching Output

2 Relay Outputs
Relay Normally Open Contact
Contact Capacity: AC 250V/3A, DC 30V/3A

Energy Pulse Output

1 Energy Pulse Output
Output Mode: Open-collector Optocoupler
Pulse Constant: 10000imp/kWh, Settable

Auxiliary Power Supply

AC/DC 85–265V
DC 24V ±20%
DC 48V ±20%
Power Consumption: ≤10VA

Environment

Operating Temperature: -25°C to +65°C
Storage Temperature: -40°C to +80°C
Humidity: ≤93%RH, Non-condensing
Altitude: ≤2500m

Wiring

amc72_wiring

Installation

amc72_installation

Typical connection

8

Communication Interface: RS485

  • System voltage

    AC 3×57.7V/100V, AC 3×220V/380V

  • Frequency

    45–65Hz Voltage Overload: 1.2× continuous, 2× for 1s Current Overload: 1.2× continuous, 10× for 1s

Technical data

ParameterValue
ProtocolModbus-RTU
Baud rate1200–38400bps
Rated CurrentAC 1A or 5A
VoltageClass 0.2 Current: Class 0.2 Active Power: Class 0.5 Active Energy: Class 0.5 Reactive Power: Class 1.0 Reactive Energy: Class 1.0
Harmonics±1%
Storage temp.-40°C to +80°C
Humidity≤93%RH, Non-condensing
Altitude≤2500m

Built-in functions

  • Display LED Digital Display System Time Display Parameter Setting and Control via Keys
  • Rated U and l Three-phase Four-wire
  • Connection Three-phase four-wire Frequency 45–65Hz Voltage
  • Communication Interface: RS485

Ask us about this model. Send us the rated values of your circuit and the supply voltage; we confirm the ordering code, wiring diagram and register list within one working day.


  • Previous:
  • Next:

  • Parameter Specification
    System 3-phase 4-wire
    Frequency 45–65Hz
    Rated Voltage AC 3×57.7V/100V, AC 3×220V/380V
    Voltage Overload 1.2× rated value continuously; 2× rated value for 1s
    Voltage Power Consumption <0.5VA
    Rated Current AC 1A or 5A
    Current Overload 1.2× rated value continuously; 10× rated value for 1s
    Current Power Consumption <0.5VA
    Voltage Accuracy Class 0.2
    Current Accuracy Class 0.2
    Active Power Accuracy Class 0.5
    Reactive Power Accuracy Class 1.0
    Active Energy Accuracy Class 0.5
    Reactive Energy Accuracy Class 1.0
    Frequency Accuracy ±0.05Hz
    Digital Input 2DI, dry contact input
    Relay Output 2DO, normally open contact
    Relay Contact Capacity AC 250V/3A; DC 30V/3A
    Energy Pulse Output 1Ep, open-collector optocoupler
    Pulse Constant 10000 imp/kWh, settable
    Communication RS485
    Protocol Modbus-RTU
    Baud Rate 1200–38400bps
    Auxiliary Power Supply AC/DC 85–265V; DC 24V ±20%; DC 48V ±20%
    Power Consumption ≤10VA
    Operating Temperature -25°C to +65°C
    Storage Temperature -40°C to +80°C
    Humidity ≤93%RH, non-condensing
    Altitude ≤2500m
    Insulation Resistance >100MΩ
    Faceplate Size 75 × 75mm
    Panel Cutout 67 × 67mm
    Depth 94.3mm
    Function AMC72-E4/KC (2DI+2DO)
    Three-phase Voltage ✓
    Zero-sequence Voltage ✓
    Three-phase Current ✓
    Zero-sequence Current ✓
    Three-phase Active Power ✓
    Total Active Power ✓
    Three-phase Reactive Power ✓
    Total Reactive Power ✓
    Three-phase Apparent Power ✓
    Total Apparent Power ✓
    Three-phase Power Factor ✓
    Total Power Factor ✓
    Frequency ✓
    Voltage Phase Angle ✓
    Voltage Unbalance ✓
    Current Unbalance ✓
    Forward / Reverse Power ✓
    Four-quadrant Energy Metering ✓
    System Time Display ✓
    2 Digital Inputs (DI) ✓
    2 Relay Outputs (DO) ✓
    Energy Pulse Output (Ep) ✓
    RS485 Communication ✓
    Modbus-RTU ✓
    Event Record (SOE) —
    Harmonic Measurement (H) —
    Analog Output —