Accuracy
Active energy: Class 0.5
Auxiliary power supply
AC 220V
Consumption
Current: Power consumption< 0.5VA;
Auxiliary power supply: power consumption≤5VA
Installation
Panel mounted
Dimension(L*W*H)
Panel size (L×W): 75*75mm
Cutout(L×W): 67*67mm
Housing (L×W×H): 66*66*94.3mm
Switch relay
DC 30V/3A AC 220V/3A
Starting current
0.3%
Technical parameter |
Value |
|||
Input |
Rated value |
AC voltage:Single phaseAC 100V,400V Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; DC voltage:1000V,300V,75mV,10V; DC current: 0-20mA,4-20mA,5A; |
||
Overload |
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second |
|||
Frequency |
45Hz~65Hz |
|||
Power consumption |
Power consumption of each voltage,current input circuit is less than 0.5VA |
|||
Accuracy |
0.5 class |
|||
Function |
Display |
LED or LCD |
||
Communication |
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc. |
|||
Alarm |
1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. |
|||
Analog |
DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) |
|||
Switching |
Input |
4 channel or 2 channel dry contact Input,built in power supply |
||
Output |
2 channel switching output,NO relay contact,capacity: 3A/30VDC,3A/250VAC |
|||
Auxiliary supply |
Voltage range |
AC/DC 85-265V |
||
Power consumption |
<5VA |
|||
Insulation resistance |
≥ 100MΩ |
|||
Power frequency withstand voltage |
Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV |
Environment |
Temperature |
Operation: -10℃~+55℃Storage: -25°C ~+70°C |
Humidity |
≤95%RH,no condensation,without corrosive gas |
|
Altitude |
≤ 2500m |
2.1 Basic & Optional Function
Type |
Basic function |
Shape |
Optional function |
AMC48-AI AMC48-AV |
Current,voltage measurement; LED |
48 Square |
RS485 communication (/C ) Analog output (/M ) |
AMC48-AI3 AMC48-AV3 |
None |
||
AMC48L-AI AMC48L-AV |
Current,voltage measurement; LCD |
1. RS485 communication (C) 2. Analog output (M) |
|
AMC48L-AI3 AMC48L-AV3 |
None |
||
AMC72-AI AMC72-AV AMC72-AI3 AMC72-AV3 |
Current,voltage measurement; LED |
72 Square |
1. RS485 communication (C) 2. Analog output (M) 3.Alarmoutput (J) 4.Analog output + RS485 communication (MC) 5. RS485 communication + switching output 2DI2DO (KC) 6.Alarm output + analog output +RS485 communication (JMC) |
AMC72-DI AMC72-DV |
DC voltage,current measurement; LED |
||
AMC72L-AI AMC72L-AV AMC72L-AI3 AMC72L-AV3 |
Current,voltage measurement; LCD |
||
AMC72L-DI AMC72L-DV |
DC voltage,current measurement; LCD |
||
AMC96-AI AMC96-AV AMC96-AI3 AMC96-AV3 |
Current,voltage measurement; LED |
96 Square |
1. RS485 communication (C) 2. Analog output (/M or 3M) 3.Alarm output (J) 4.Analog output + RS485 communication (MC or M3C) 5. RS485 communication + switching 4DI2DO (KC) |
AMC96L-AI AMC96L-AV AMC96L-AI3 AMC96L-AV3 |
Current,voltagemeasurement; LCD |
Note:
1. AI/AV means single-phase current/voltage, AI3/AV3 means three-phase current/voltage.
2. /J means 1 channel relay output (multiplexing with second channel switching output).