head_banner_pro

ADL3000-E Din-rail 3-phase Programmable energy meter

● AC 3×220/380V,3×380V,3×57.7/100V,3×100V

● 3×1(6)A,3×10(80)A

● U、I、P、Q、S、PF、kWh、kvarh

● RS485(MODBUS-RTU)

● LCD display

● Frozen data

● 2-31st Harmonics

● kWh Class 0.5S,kVarh Class 2


Information

Parameter

Function

Download

Characteristic

1

LCD Display

2

Function

3
4

Appearance

5

Wiring

6
7

Application installation diagram

8

The secondary access

Installation

9
10
11

Typical connection

12
13

  • Previous:
  • Next:

  • 1. Technical parameter

    Specification

    3 phase 3 wires, 3 phase 4 wires

    Voltage

    Reference voltage

    3×100V、 3×380V、3×57.7/100V、 3×220/380V

    Consumption

    <10VA(Single phase)

    Impedance

    >2MΩ

    Accuracy class

    Error±0.2%

    Current

    Input current

    3×1(6)A,3×1(6)A(Outlay transformer),3×10(80)A,3×10(100)A(Outlay transformer)

    Consumption

    <1VA(Single phase rated current)

    Accuracy class

    Error±0.2%

    Power

    Active, reactive, apparent power, error±0.5℅

    Frequency

    45~65Hz, Error±0.2%

    Temperature

    -40℃~99℃

    Energy

    Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2)

    Clock

    ≤0.5s/d

    Energy pulse output

    1 active optocoupler output, 1 reactive optocoupler output

    Switching output

    1 Switching output, Maximum allowed voltage: DC/AC 220V

    Switching input

    1 optocoupler input,Maximum allowed voltage: DC/AC 220V

    Width of pulse

    80±20ms

    Pulse constant

    6400imp/kWh,400imp/kWh(Correspond with the basic current)

    Interface and communication

    RS485:Modbus RTU

    Range of communication address

    Modbus RTU:1~ 247;

    Baud rate

    1200bps~19200bps

    Relative temperature

    -25℃~+55℃

    Relative humidity

    ≤95℅(No condensation)

    2. Basic & Optional Function

    Function

    Function description

    Function provide

    Measurement of kWh

    Active kWh (positive and negative)

    Reactive kWh (positive and negative)

    A, B, C phase positive active kWh

    Measurement of electrical parameters

    U、IP、Q、S、PF、F

    Measurement of

    2~31ST Voltage and current harmonic

    LCD Display

    8 bits section LCD display, background light

    Key programming

    4 keys to communication and set parameters

    Pulse output

    Active pulse output

    Reactive pulse output

    □Note 1

    Clock pulse output

    □Note 1

    Multi-tariff and functions

    Active switch input

    □Note2

    Switch output

    □Note 2

    Adapt 4 time zones, 4 time interval lists, 14 time interval by day and 4 tariff rates

    Max demanded kWh and time happened

    Frozen data on last 48 months, last 90days

    Date, time

    Communication

    Infrared communication

    The first communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU

    The second communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU

    □Note 2

    Temperature measurement

    Support 3 outlay NTC temperature

    □Note 3

    “■” means standard, “□” means optional.

    Note:

    1. Reactive pulse output, clock pulse output and switching output: Choose one of these three.

    2. Active switching, the second communication path: Choose one of these two.

    3. Both 1 and 2 cannot be chosen while choosing temperature measurement.